SEC Info  
    Home      Search      My Interests      Help      Sign In      Please Sign In

Ormat Technologies, Inc. – IPO: ‘S-1/A’ on 9/28/04 – EX-10.3.34

On:  Tuesday, 9/28/04, at 9:30am ET   ·   Accession #:  950136-4-3123   ·   File #:  333-117527

Previous ‘S-1’:  ‘S-1’ on 7/21/04   ·   Next:  ‘S-1/A’ on 10/22/04   ·   Latest:  ‘S-1/A’ on 11/10/04   ·   2 References:   

Find Words in Filings emoji
 
  in    Show  and   Hints

  As Of                Filer                Filing    For·On·As Docs:Size              Issuer               Agent

 9/28/04  Ormat Technologies, Inc.          S-1/A                 90:15M                                    Capital Systems 01/FA

Initial Public Offering (IPO):  Pre-Effective Amendment to Registration Statement (General Form)   —   Form S-1
Filing Table of Contents

Document/Exhibit                   Description                      Pages   Size 

 1: S-1/A       Amendment 1 to Form S-1                             HTML   3.29M 
 2: EX-1.1      Form of                                             HTML    194K 
11: EX-10.1.10  Amendment # 1 to Loan Agreement                     HTML     27K 
12: EX-10.1.11  Capital Note                                        HTML     22K 
13: EX-10.1.12  Amendment No. 1 to Capital Note                     HTML     22K 
14: EX-10.1.13  Guarantee Fee Agreement                             HTML     22K 
15: EX-10.1.14  Reimbursement Agreement                             HTML     25K 
16: EX-10.1.15  Services Agreement                                  HTML     40K 
 3: EX-10.1.2   Amended and Restated Bridge Loan Agreement          HTML    100K 
 4: EX-10.1.3   Bank Hapoalim Credit Facility Agreement             HTML    386K 
 5: EX-10.1.4   Credit Agreement Dtd 12/31/02                       HTML    730K 
 6: EX-10.1.5   Credit Agreement Dtd 12/18/03                       HTML   1.09M 
 7: EX-10.1.6   Eximbank Credit Agreement                           HTML    557K 
 8: EX-10.1.7   Indenture                                           HTML    703K 
 9: EX-10.1.8   First Supplemental Indenture                        HTML     39K 
10: EX-10.1.9   Loan Agreement                                      HTML     38K 
84: EX-10.10    Indemnification Agreement                           HTML     46K 
17: EX-10.2.1   Purchase and Sale Agreement                         HTML    360K 
18: EX-10.3.1   Power Purchase Contract                             HTML    121K 
23: EX-10.3.11  Amended and Restated Power Purchase and Sale Agmt   HTML    237K 
24: EX-10.3.13  Power Purchase Contract                             HTML    197K 
25: EX-10.3.14  Amendment No. 1 Power Purchase Contract             HTML     64K 
26: EX-10.3.16  Power Purchase Contract Dtd 4/16/85                 HTML    206K 
27: EX-10.3.17  Amend 1 to Power Purchase Contract Dtd 10/25/85     HTML     46K 
28: EX-10.3.18  Amend 2 to Power Purchase Contract Dtd 12/20/89     HTML     25K 
29: EX-10.3.19  Interconnections Facilities Agreement               HTML     77K 
30: EX-10.3.20  Interconnection Facilities Agreement                HTML     35K 
31: EX-10.3.21  Interconnection Facilities Agreement                HTML     58K 
32: EX-10.3.22  Interconnection Agreement                           HTML     31K 
33: EX-10.3.23  Plant Connection Agreement                          HTML     58K 
34: EX-10.3.24  Plant Connection Agreement                          HTML     96K 
35: EX-10.3.25  Transmission Service Agreement                      HTML     87K 
36: EX-10.3.26  Plant Connection Agreement                          HTML     53K 
37: EX-10.3.27  Plant Connection Agreement                          HTML     61K 
38: EX-10.3.28  Plant Connection Agreement                          HTML     64K 
39: EX-10.3.29  Plant Connection Agreement                          HTML    186K 
19: EX-10.3.3   Power Purchase Contract                             HTML    111K 
40: EX-10.3.30  Plant Connection Agreement                          HTML    187K 
41: EX-10.3.31  Transmission Service Agreement                      HTML     81K 
42: EX-10.3.32  Transmission Service Agreement                      HTML     83K 
43: EX-10.3.33  Transmission Service Agreement                      HTML     85K 
44: EX-10.3.34  Transmission Service Agreement                      HTML    100K 
45: EX-10.3.35  Plant Amendment No. 1                               HTML     28K 
46: EX-10.3.39  Agreement Addressing Renewable Energy Pricing       HTML     74K 
47: EX-10.3.40  Amnd No.1 to Agrt Address Renewable Energy Pricing  HTML     58K 
48: EX-10.3.41  Agreement Addressing Renewable Energy Pricing       HTML     72K 
49: EX-10.3.42  Amend No. 1 to Agrnt Addr Renewable Energy Pricing  HTML     64K 
50: EX-10.3.43  Energy Services Agreement                           HTML     79K 
51: EX-10.3.44  Purchase Power Contract, Dated March 24, 1986       HTML     92K 
52: EX-10.3.45  Firm Capacity Amendment                             HTML     78K 
53: EX-10.3.46  Amendment to Purchase Power Contract                HTML     32K 
54: EX-10.3.47  Third Amendment to Purchase Power Contract          HTML     76K 
55: EX-10.3.48  Performance Agreement                               HTML    167K 
56: EX-10.3.49  Agreement to Design 69 Kv Transmission Lines        HTML     79K 
20: EX-10.3.5   Amendment #1 to Power Purchase and Sales Agreement  HTML     49K 
21: EX-10.3.6   Settlement Agreement                                HTML     37K 
22: EX-10.3.7   Power Purchase Contract Dtd 4/16/85                 HTML    155K 
57: EX-10.4.1   Ormesa Blm Geothermal Resources Lease               HTML    160K 
63: EX-10.4.12  Lease Agreement, Dated 3/17/64                      HTML     89K 
64: EX-10.4.13  Lease Agreement, Dated 2/16/64                      HTML     72K 
65: EX-10.4.18  Geothermal Lease Agreement, Dated 7/18/79           HTML     79K 
66: EX-10.4.19  Lease Agreement                                     HTML     82K 
58: EX-10.4.2   Ormesa Blm License for Electric Power Plant         HTML     42K 
67: EX-10.4.20  Lease Agreement, Dated 6/14/71                      HTML     56K 
68: EX-10.4.21  Lease Agreement                                     HTML     63K 
69: EX-10.4.23  Geothermal Lease Agreement                          HTML     55K 
70: EX-10.4.24  Geothermal Lease Agreement, Dated 8/31/83           HTML    128K 
71: EX-10.4.26  Geothermal Resources Lease - Guisti                 HTML     55K 
72: EX-10.4.27  Amendment to Geothermal Lease                       HTML     27K 
73: EX-10.4.28  Second Amendment to Geothermal Lease                HTML     39K 
74: EX-10.4.29  Geothermal Resources Sublease                       HTML    144K 
59: EX-10.4.3   Geothermal Resources Mining Lease, Dated 2/20/81    HTML    126K 
75: EX-10.4.30  Klp Lease                                           HTML    265K 
76: EX-10.4.31  Klp Lease Amendment No. 1                           HTML    341K 
77: EX-10.4.32  Second Amendment to Klplease                        HTML     25K 
60: EX-10.4.4   Geothermal Lease Agreement, Dated 10/20/75          HTML     55K 
61: EX-10.4.5   Geothermal Lease Agreement                          HTML     78K 
62: EX-10.4.6   Geothermal Resources Lease, Dated 11/18/83          HTML     77K 
78: EX-10.5.1   Engineering, Procurement and Construction Contract  HTML    434K 
79: EX-10.5.3   Engineering, Procurement and Construction Contract  HTML   1.00M 
80: EX-10.5.4   Patent License Agreement                            HTML    144K 
81: EX-10.7     Executive Employment Agreement of Lucien Bronicki   HTML     70K 
82: EX-10.8     Exec Employment Agreement of Yehudit Bronicki       HTML     75K 
83: EX-10.9     Executive Employment Agreement of Yoram Bronicki    HTML     82K 
85: EX-23.1     Consent of Independent Accountants                  HTML     22K 
86: EX-23.3     Consent of Dani Falk                                HTML     21K 
87: EX-23.4     Consent of Edward Muller                            HTML     21K 
88: EX-23.5     Consent of Lester P. Silverman                      HTML     21K 
89: EX-23.6     Consent of Jacob Worenklein                         HTML     21K 
90: EX-99.3     Material Terms Deviations                           HTML     21K 


EX-10.3.34   —   Transmission Service Agreement
Exhibit Table of Contents

Page (sequential) | (alphabetic) Top
 
11st Page   -   Filing Submission
2IID-Edison Transmission Service Agreement for Alternative Resources
3Table of Contents

This exhibit is an HTML Document rendered as filed.  [ Alternative Formats ]

EX-10.3.341st Page of 42TOCTopPreviousNextBottomJust 1st
 


EX-10.3.342nd Page of 42TOC1stPreviousNextBottomJust 2nd
Exhibit 10.3.34 Schedule A Item 29 IID - EDISON TRANSMISSION SERVICE AGREEMENT FOR ALTERNATIVE RESOURCES BETWEEN IMPERIAL IRRIGATION DISTRICT AND SOUTHERN CALIFORNIA EDISON COMPANY
EX-10.3.343rd Page of 42TOC1stPreviousNextBottomJust 3rd
TABLE OF CONTENTS Section Title Page 1 PARTIES 1 2 RECITALS 1 3 AGREEMENT 2 4 DEFINITIONS 2 5 TERM 5 6 TRANSMISSION SERVICE 6 7 TRANSMISSION LOSSES 10 8 CHARGES 11 9 BILLING AND PAYMENT 13 10 LIABILITY 15 11 AUDITING 18 12 AUTHORIZED REPRESENTATIVES 18 13 NO DEDICATION OF FACILITIES 19 l's HON-WAIVER 19 15 NO THIRD PARTY RIGHTS 19 16 UNCONTROLLABLE FORCES 19 17 ASSIGNMENTS 21 18 GOVERNING LAW 21 19 NOTICES 21 20 SIGNATURE CLAUSE 23
EX-10.3.344th Page of 42TOC1stPreviousNextBottomJust 4th
TABLE OF CONTENTS Page EXHIBIT I - DEVELOPMENTS AND METHODOLOGIES FOR TRANSMISSION AND SUBTRANSMISSION SERVICE CHARGES AND SCHEDULING FEE (EI-1-EI-14) EXHIBIT II - TRANSMISSION SERVICE FOR EI-15 THE BRAWLEY GEOTHERMAL POWER PLANT UNIT NO. 1 EXHIBIT III - TRANSMISSION SERVICE FOR THE EI-16 SALTON SEA GEOTHERMAL POWER PLANT UNIT NO. 1 EXHIBIT IV - TRANSMISSION SERVICE FOR THE EI-17 MAGMA EAST MESA GEOTHERMAL POWER PLANT UNIT NO. I EXHIBIT V - TRANSMISSION SERVICE FOR THE EI-18 HEBER GEOTHERMAL POWER PLANT UNIT NO. 1 EXHIBIT VI - TRANSMISSION SERVICE FOR EI-19 THE VULCAN POWER GEOTHERMAL POWER PLANT UNIT NO. 1 EXHIBIT VII - TRANSMISSION SERVICE FOR THE EI-20 WESTERN POWER GROUP BIOMASS POWER PLANT UNIT NO. 1 EXHIBIT VIII- TRANSMISSION SERVICE FOR EI-21 THE ORMESA GEOTHERMAL POWER PLANT UNIT NO. 1
EX-10.3.345th Page of 42TOC1stPreviousNextBottomJust 5th
IID - EDISON TRANSMISSION SERVICE AGREEMENT FOR ALTERNATIVE RESOURCES 1. PARTIES: The Parties to this Agreement are Imperial Irrigation District, organized under the Water Code of the State of California ("IID"), and Southern California Edison Company, a California corporation ("Edison"), hereinafter sometimes referred to individually as "Party," and collectively as "Parties". 2. RECITALS: This Agreement is made with reference to the following facts, among others: 2.1 Edison plans to develop its own alternative resource facilities and/or purchase the electrical output from Third Party alternative resource facilities located in IID's service area. 2.2 Edison and the Third Parties require transmission service from IID to deliver the output from such alternative resource facilities to Edison's electrical system. 2.3 In a Letter Agreement executed on November 22, 1983, the Parties agreed to establish an intertie connecting the Parties' electrical systems to facilitate exchanges of power. The Parties also agreed to develop and execute a transmission service agreement to provide transmission for Edison's power to its electrical system over IID's existing or upgraded electrical system.
EX-10.3.346th Page of 42TOC1stPreviousNextBottomJust 6th
2.4 In a Letter Agreement executed on December 7, 1982, the Parties agreed to develop certain transmission facilities at 230 kilovolts to provide for the export of alternative resource facilities electrical output from the Imperial Valley to Edison's electrical system. 2.5 Edison desires to purchase transmission service for the electrical output from the alternative resource facilities and IID is willing to sell said service to Edison. 3. AGREEMENT: The Parties agree as follows: 4. DEFINITIONS: The following terms, when used herein with initial capitalization, whether in the singular or the plural, shall have the meanings specified: 4.1. Agreement: This "IID-Edison Transmission Service Agreement for Alternative Resources" between Southern California Edison Company and Imperial Irrigation District, and all Exhibits, as such Agreement may subsequently be amended. 4.2 Authorized Representative: The representative of a Party designated in accordance with Section 12. 4.3 Blythe Substation: Western's electrical 161 kilovolt (kV) substation at Blythe, California where IID's existing 161 kV "F" transmission line terminates. 4.4 Coachella-Mirage Line: Approximately 20.6 miles of 230 kV transmission line that IID shall cause to be constructed and that shall be owned by IID. Such line is to 2
EX-10.3.347th Page of 42TOC1stPreviousNextBottomJust 7th
be constructed between Coachella Valley Substation and Mirage Substation. The line is anticipated to be in operation on or before June 1, 1986, or as soon thereafter as practicable. 4.5 Coachella Valley Substation: IID's electrical substation located within its Control Area and scheduled to be a terminal point for the Coachella- Mirage Line. 4.6 Control Area: All or part of a Party's electrical generation resources, transmission facilities and distribution facilities, or a combination thereof with those of other utilities, agencies or poo1s to which a common automatic generation control scheme is applied. 4.7 Date of Initial Service: The date when the Plant output is first available for delivery to Edison and as provided to IID pursuant to Section 5.2. Such date shall be deemed to be May 1, 1986, for the Plants specified in Exhibits II, III, and IV. 4.8 Mirage Substation: Edison's electrical 230/115/92 kV substation located approximately eight miles west of the City of Indio and one and one-half miles north of Interstate Highway 10 where the Points of Interconnection are located and where the Coachella-Mirage Line terminates. 4.9 Normal Transmission Capacity: The maximum electrical power transfer ability, expressed in megawatts (MW), available to IID to transmit IID's electrical power and to provide the transmission service. Such transfer ability, as determined by IID, in its 3
EX-10.3.348th Page of 42TOC1stPreviousNextBottomJust 8th
sole judgment, shall be consistent with prudent operating procedures and with generally-accepted engineering and operating practices in the electrical utility industry. 4.10 Operating Transmission Capability: The maximum electrical power transfer ability, expressed in megawatts (MW), available to IID at any given time to transmit IID's electrical power and to provide the transmission service. Such transfer ability shall be as determined by IID in its sole judgment, may vary from time-to-time depending on system conditions, and shall be consistent with prudent operating procedures and generally-accepted engineering and operating practices in the electrical utility industry. 4.11 Plant(s): The electrical generating alternative resource facilities developed by Edison or Third Parties for which IID shall provide transmission service is specified in Exhibits II, III, IV, V, VI, VII, VIII and in any subsequent Plant Amendment(s). 4.12 Plant Amendment(s): The agreement(s) reached by the Parties, as amendments to this Agreement, for transmission service to be provided by IID for each Plant added by Edison or for Edison's account subsequent to the execution of this Agreement. 4.13 Plant Connection Agreement(s): The agreement(s) between IID and Third Parties or Edison providing for the connection of the Plant(s) to IID's electrical system as specified in Exhibits II, III, IV, V, VI, VII, VIII and in any subsequent Plant Amendment(s). 4
EX-10.3.349th Page of 42TOC1stPreviousNextBottomJust 9th
4.14 Point of Delivery: The Points of Interconnection, Blythe Substation or other points as agreed to by the Authorized Representatives as delivery points and as specified in Exhibits II, III, IV, V, VI, VII, VIII and in any subsequent Plant Amendments. 4.15 Points of Interconnection: The 115/92 kV switchrack at the Mirage Substation site where Edison's 115 kV facilities are attached to IID's 92 kV facilities or the 230 kV switchrack where Edison's 230 kV facilities shall be attached to the Coachella-Mirage Line. 4.16 Point of Receipt: The point at which IID receives the electrical output from each Plant for Edison or for Edison's account, as specified in Exhibits Il, III, IV, V, VI, VII, VIII and in any subsequent Plant Amendments. 4.17 Third Parties: Developers and/or operators of facilities using alternative resources including biomas, waste, wind, solar, geothermal and water to produce electrical energy. Such developers and/or operators are not signatories to this Agreement. 4.18 Transmission Service Entitlement: The amount of transmission service, expressed in megawatts (MW), provided by IID to Edison from a Point of Receipt to the Point(s) of Delivery. 4.19 Western: The United States Department of Energy Western Area Power Administration. 5
EX-10.3.3410th Page of 42TOC1stPreviousNextBottomJust 10th
5. TERM: 5.1 Unless otherwise agreed to by the Parties, this Agreement shall be effective upon execution by the Parties and shall remain in effect until the earlier of December 31, 2015 or the termination date of the last Plant Connection Agreement. 5.2 The Transmission Service Entitlement to be provided by IID for each Plant shall be contingent on a Plant Connection Agreement being in effect. Transmission service shall commence on the Date of Initial Service of such Plant(s). If not already specified in Section 4.7, Edison's Authorized Representative shall provide the Date of Initial Service to IID's Authorized Representative in a thirty (30) days' written notice in advance of the Date of Initial Service. 6. TRANSMISSION SERVICE: 6.1 Subject to the terms of this Agreement, IID shall provide to Edison and Edison shall purchase from IID transmission service over IID's transmission system for the Plant(s) herein. 6.2 The Transmission Service Entitlement for each Plant shall be the amount either specified In Exhibits II, III, IV, V, VI, VII, VIII and in any subsequent Plant Amendment(s), or the amount provided to IID's Authorized Representative by Edison's Authorized Representative in a thirty (30)-day advance written notice prior to the Date of Initial Service. Except for the Plants specified in Exhibits II, III and IV, the Transmission 6
EX-10.3.3411th Page of 42TOC1stPreviousNextBottomJust 11th
Service Entitlement to be provided by IID subsequent to the Date of Initial Service may be adjusted semi-annually until the Plant(s) has/have operated for two years. Such adjustment shall be made by having Edison's Authorized Representative give IID'S Authorized Representative a ninety (90)-day advance written notice as to the adjustment required. At the end or the two-year operating period for such Plant(s), the Transmission Service Entitlement shall remain as established or as redetermined by the Authorized Representatives and shall subsequently be fixed for the remainder of the terms specified in Exhibits II, III, IV, V, VI, VII, VIII and in any subsequent Plant Amendment(s). The Transmission Service Entitlement shall not be changed unless otherwise agreed to by the Authorized Representatives. 6.3 IID reserves the right to interrupt or curtail the transmission service provided hereunder as follows: 6.3.1 If the Operating Transmission Capability is reduced to less than normal Transmission Capacity from a Point of Receipt to a Point of Delivery, and when continuity of service within IID's Control Area is not being jeopardized, IID may curtail the transmission service currently being provided from such Point of Receipt to such Point of Delivery, to an amount "A" determined by the following formula: A = Operating Transmission Capability x Transmission Service --------------------------------- Entitlement Normal Transmission Capacity 7
EX-10.3.3412th Page of 42TOC1stPreviousNextBottomJust 12th
The transmission service for each Plant shall be curtailed by multiplying the Transmission Service Entitlement in accordance with Exhibits II, III, IV, V, VI, VII, VIII and in any subsequent Plant Amendments by the same percentage (expressed as a decimal) as used in the determination of "A". However, any such curtailment shall occur only after IID has made all reasonable efforts to eliminate the cause of the reduction in Operating Transmission Capability, and IID shall then employ reasonable efforts to eliminate expeditiously the cause of said reduction. 6.3.2 If continuity of service within IID's Control Area is being jeopardized, as determined by IID in its sole judgment, IID may interrupt or curtail the transmission service provided hereunder to the extent necessary to avoid or eliminate such jeopardy; provided, (i) that such interruptions or curtailments may be made so that IID may fully utilize all generating resources owned by it or available to it under contract in order to avoid damage to IID's electrical system caused by overloading, (ii) that no such interruption or curtailment may be made by IID in order that IID may acquire all or any portion of Edison's capacity or energy available to Edison under contract without Edison's prior consent, and (iii) that such interruption or curtailment shall occur only after IID has made all reasonable efforts to avoid or eliminate such jeopardy. 6.4 If IID's efforts do not avoid or eliminate such jeopardy, the Parties shall endeavor to develop some other arrangements to avoid or eliminate such jeopardy and minimize the effects of IID's interruption or curtailment to both to Parties' Control Areas. 8
EX-10.3.3413th Page of 42TOC1stPreviousNextBottomJust 13th
6.5 Subject to Section 6.8, and in the event of any curtailments or interruptions made pursuant to Section 6.3.1 or Section 6.3.2, Edison shall, immediately after being orally satisfied by IID, reduce its energy schedules by the amounts requested by IID. 6.6 The transmission service to be provided by IID and purchased by Edison for each Plant shall not exceed the Transmission Service Entitlement. 6.7 Subject to Section 6.3, IID shall, during the periods that IID has agreed to provide the transmission service at the specified Transmission Service Entitlements, accept hourly scheduled energy deliveries at the Point of Receipt and simultaneously deliver the same amount of energy to Edison or for Edison's account at the Point(s) of Delivery mutually agreed upon by the Parties' dispatchers and/or schedulers. Unless otherwise agreed to by the Authorized Representatives, the total sum of Transmission Service Entitlements to the Points of Delivery specified below shall not exceed 150 MV. However, in no case shall the Transmission Service Entitlement to a specified Point of Delivery exceed the following: Blythe Substation 161 kV: 110 MV Mirage Substation 115/92 kV: 35 MW Mirage Substation 230 kV: 150 MW' Edison shall provide IID an executed copy of its transmission service agreement with Western. 9
EX-10.3.3414th Page of 42TOC1stPreviousNextBottomJust 14th
6.8 Hourly scheduled energy deliveries shall be in accordance with the provisions of this Agreement. The hourly schedules shall conform with the practices and procedures developed by the Parties' dispatchers and schedulers and agreed to by the Authorized Representatives. IID shall coordinate the hourly scheduled energy deliveries from the Plant(s) until such time that dynamic scheduling may be arranged and procedures for such may be agreed to by the Authorized Representatives. 7. TRANSMISSION LOSSES: ------------------- 7.1 IID shall determine, by transmission power flow analysis, the electrical losses (expressed as a percent amount of hourly scheduled energy deliveries) associated with the electrical output from each Plant. Such analysis may be performed by IID, at its sole expense, and as deemed necessary by changing conditions on IID's electrical system. The initial percent amount, for each Plant, representing the electrical losses as determined herein shall be as specified in Exhibits II, III, IV, V, VI, VII, VIII and in any subsequent Plant Amendment(s). 7.2 Unless otherwise agreed to by Edison's and IID's schedulers and dispatchers, IID shall reduce the amount of all hourly scheduled energy deliveries to Edison or for Edison's account by the percent amount of such hourly deliveries for each Plant in accordance with Exhibits II, III, IV, V, VI, VII, VIII and in any subsequent Plant Amendment(s) plus a transformer loss percent amount if delivered at the Mirage Substation 115/92 kV switchrack. 10
EX-10.3.3415th Page of 42TOC1stPreviousNextBottomJust 15th
7.3 It either Party believes that there has been a significant change in IID's electrical system and the electrical losses associated with any Plant should be redetermined, either Party's Authorized Representative may submit a written request ________ the other Party's Authorized Representative that the electrical losses be redetermined. Following such request, a transmission flow analysis may be performed by IID as approved by the Authorized Representatives and paid for by the requesting Party. If the percent amount for electrical losses is redetermined, such percent amount shall become effective as of the first day of the month following the date of such redetermination; provided, that such a redetermination may be no sooner than twelve (12) months after the most recent redetermination. Any redetermination of electrical losses made pursuant to this Section 7 shall be based on conditions in existence at the time of such redetermination. 7.4 Along with the monthly billing pursuant to Section 9.1, for the transmission service for each Plant, IID shall submit a monthly summary of hourly scheduled energy deliveries and of electrical losses for each Plant. 8. CHARGES: 8.1 For transmission service provided by IID, Edison shall pay IID at an initial rate of $1.14 per kilowatt per month for transmission service over IID's 92 kV-161 kV- 230 kV transmission system plus the appropriate initial rate specified in Exhibit I.B for transmission service over IID's 34.5 kV subtransmission system as applicable. The total 11
EX-10.3.3416th Page of 42TOC1stPreviousNextBottomJust 16th
charge for transmission service shall be determined by the sum of the products of such applicable rates times the Transmission Service Entitlements. The initial rate for the 92 kV-161 kV-230 kV transmission system and the initial rate for the 34.5 kV subtransmission system has been determined by IID pursuant to the methodologies specified in Exhibit I.A and Exhibit I.B respectively. Any specific facility charge to the Third Parties or to Edison for connecting the Plant(s) to the IID transmission system(s) shall be included only in the Plant Connection Agreement(s) between IID and the Third Parties or Edison. 8.2 Both the 92 kV-161 kV-230 kV transmission and 34.5 kV subtransmission system rates shall be reviewed annually and may be revised. Such review and revision, if necessary, shall commence effective January 1, 1986. Any revision of the rates shall be based on the methodologies in Exhibit I.A-2 and Exhibit I.B.A and on the conditions in existence at the time of the revision. Edison shall have the right to review any exhibits or work papers prepared by IID to revise the rates prior to the effective date(s) of the revision. 8.3 An initial monthly scheduling fee, as specified in Exhibits II, III, IV, V, VI, VII, VIII and in any subsequent Plant Amendment(s), shall be paid by Edison to IID for those months in which there were scheduled energy deliveries from the Plant(s). The initial scheduling fee has been determined by IID pursuant to the methodology specified in Exhibit I.C. The scheduling fee shall be reviewed annually and may be revised. Such 12
EX-10.3.3417th Page of 42TOC1stPreviousNextBottomJust 17th
review and revision, if necessary, shall commence effective January 1, 1986. Any revision of the scheduling fee shall be based on the methodology in Exhibit I.C and on the conditions in existence at the time of the revision. Edison shall have the right to review any exhibits or work papers prepared by IID to revise the scheduling fee prior to the effective date of the revision. 9. BILLING AND PAYMENT: ------------------- 9.1 IID shall render bills to Edison, beginning in the month of the Date of Initial Service, on or before the fifteenth (15th) day of each month for the transmission service to be provided during the month. Edison shall pay such bills within twenty (20) days after receipt thereof. All payments by Edison shall be sent to: Imperial Irrigation District c/c Manager, Finance & Accounting P.O. Box 937 Imperial, CA 92251 All billings by IID shall be sent to: Southern California Edison Company c/o Manager of Cogeneration and Small Power Development P.O. Box 800 Rosemead, CA 91770 13
EX-10.3.3418th Page of 42TOC1stPreviousNextBottomJust 18th
9.2 Either Party's Authorized Representative may at any time, by advance written notice to the other Party's Authorized Representative, change the address to which payments or billings shall be sent. 9.3 Bills which are not paid in full by said due date shall thereafter bear an additional charge of one and one-half percent (1 1/2%) per month, or the maximum legal rate of interest, whichever is less, compounded monthly on the unpaid amount prorated by days from the due date until payment is received by IID. 9.4. In the event any portion of any bill is disputed, the disputed amount shall be paid when due under protest. If the protested portion of the payment is found to be incorrect by the Authorized Representatives, the disputed amount shall be paid by IID to Edison, including interest at the rate of 1-1/2% per month, or the maximum legal rate, whichever is less, compounded monthly from the date of payment by Edison to the date the refund check or adjusted bill is received by Edison. 9.5 For a fractional part of a calendar month at the beginning or end of the period for which the transmission service is provided hereunder, the charge pursuant to Section 8.1 shall be proportionately adjusted by the ratio of days that service is furnished by IID to Edison during such month to the total number of days in such month. 9.6 The charge for the transmission service pursuant to Section 8.1 shall be proportionately reduced to the extent the duration of interruptions or curtailments of the 14
EX-10.3.3419th Page of 42TOC1stPreviousNextBottomJust 19th
transmission service which may occur pursuant to Section 6.3.2 exceed a cumulative total of twenty-four (24) hours during any calendar month based on 730 hours per month representing the full transmission service charge. The amount of such prorata reduction in any month shall reflect the duration and amount of such interruptions or curtailments which exceed said cumulative 24 hours. Such prorata reduction shall be reflected as a credit to Edison as soon as possible in a subsequent monthly bill. 9.7 The charge for the transmission service shall not be reduced if IID can deliver, but Edison cannot receive the hourly scheduled energy deliveries independent of the duration of time this condition exists. 10. LIABILITY: 10.1 Except for any loss, damage, claim, cost, charge or expense resulting from Willful Action, neither Party, its directors or other governing body, officers or employees shall be liable to the other Party for any loss, damage, claim, cost, charge, or expense of any kind or nature incurred by the other Party (including direct, indirect or consequential loss, damage, claim, cost, charge or expense; and whether or not resulting from the negligence of a Party, its directors or other governing body, officers, employees or any person or entity whose negligence would be imputed to such Party) from engineering, repair, supervision, inspection, testing, protection, operation, maintenance, replacement, reconstruction, use or ownership of such Party's electrical system in connection with implementation of this Agreement. Except for any loss, damage, claim, cost, charge or 15
EX-10.3.3420th Page of 42TOC1stPreviousNextBottomJust 20th
expense resulting from Willful Action, each Party releases the other Party, its directors or other governing body, officers and employees from any such liability. 10.2 Except for liability resulting from Willful Action of the other Party, a Party whose electrical customer shall make a claim or bring an action for any death, injury, loss or damage arising out of delivery of, interruptions to or curtailment of electrical service to such customer caused by performance or nonperformance of a Party's obligations hereunder shall indemnify and hold harmless the other Party, its directors or other governing body, officers and employees from and against any liability for such death, injury, loss or damage. As used in this Agreement, the term "electrical customer" shall mean an electrical consumer, except an electrical utility system to whom power is delivered for resale. 10.3 For the purpose of this Section 10, Willful Action shall be defined as action taken or not taken by a Party at the direction of its directors or other governing body, officers or employees having management or administrative responsibility affecting its performance under this Agreement, as follows: 10.3.1 Action which is knowingly or intentionally taken or failed to be taken with conscious indifference to the consequences thereof or with intent that injury or damage would result or would probably result therefrom. 16
EX-10.3.3421st Page of 42TOC1stPreviousNextBottomJust 21st
10.3.2 Action which has been determined by final arbitration award or final judgment or judicial decree to be a material default under this Agreement and which occurs or continues beyond the time specified in such arbitration award or judgment or judicial decree for curing such default or, if no time to cure is specified therein, occurs or continues thereafter beyond a reasonable time to cure such default. 10.3.3 Action which is knowingly or intentionally taken or not taken with the knowledge that such action taken or not taken is a material default under this Agreement. 10.4 Willful Action does not include any act or failure to act which is merely involuntary, accidental or negligent. 10.5 The phrase "employees having management or administrative responsibility", as used in Section 10.3, means the employees of a Party who are responsible for one or more of the executive functions of planning, organizing, coordinating, directing, controlling and supervising such Party's performance under this Agreement with responsibility for results. 11. AUDITING: 11.1 IID shall make its books, records, and other supporting information, as requested, available to Edison or to Edison's designated contracted representative(s) with a CPA firm, for the purpose of auditing any charges or accounts to be kept by IID 17
EX-10.3.3422nd Page of 42TOC1stPreviousNextBottomJust 22nd
hereunder. All such audits shall be undertaken at reasonable times and in conformance with generally-accepted auditing standards. 11.2 If as a result of such audits Edison believes its charges or accounts should be adjusted, the findings shall be presented to the Authorized Representatives. If the Authorized Representatives agree that any audit finding should result in a revision of charges or accounts, such revisions shall be retroactive to the first billing for such charges and accounts and shall be made as soon as practical after determination. 11.3 The amount of any unresolved dispute shall accrue interest at the rate of one and one-half percent (1 1/2%) per month, or the maximum legal rate, whichever is less, compounded monthly for any amount of money ultimately refunded to Edison. 12. AUTHORIZED REPRESENTATIVES: Within thirty (30) calendar days after the date of execution of this Agreement, each Party shall designate by written notice to the other Party a representative who is authorized to act on its behalf in the implementation of' this Agreement. Either Party may at any time change the designation of its Authorized Representative by written notice to the other Party. 13. NO DEDICATION OF FACILITIES: Any undertaking by one Party to the other Party under any provision of this Agreement shall not constitute the dedication of the system or any portion thereof of the Party to the public or to the other Party, and it is 18
EX-10.3.3423rd Page of 42TOC1stPreviousNextBottomJust 23rd
understood and agreed that any such undertaking under any provision of this Agreement by a Party shall cease upon the termination of its obligations hereunder. 14. NON-WAIVER: None of the provisions of this Agreement shall be considered waived by either Party except when such waiver is given in writing. The failure of either Party to insist in any one or more instances upon strict performance of any of the provisions of this Agreement or to take advantage of arty of its rights hereunder shall not be construed as a waiver of any such provisions or the relinquishment of any such rights for the future, but the same shall continue and remain in full force and effect. 15. NO THIRD PARTY RIGHTS: The Parties do not intend to create rights in or to grant remedies to any hird Party or others as a beneficiary of this Agreement or of any duty, covenant, obligation or undertaking established hereunder. 16. UNCONTROLLABLE FORCES: Neither Party shall be considered to be in default in the performance of any of its obligations under this Agreement where a failure of performance shall be due to an uncontrollable force. The term "uncontrollable force" shall mean any cause beyond the control of the Party affected including, but not restricted to, failure of or threat of failure of facilities which have been maintained in accordance with generally-accepted engineering and operating practices in the electrical utility industry, flood, drought, earthquake, tornado, storm, fire, pestilence, lightning and other natural catastrophes, epidemic, war, riot, civil disturbance or disobedience, strike, labor 19
EX-10.3.3424th Page of 42TOC1stPreviousNextBottomJust 24th
dispute, labor or material shortage, sabotage, government priorities and restraint by court order or public authority (whether valid or invalid) and action or nonaction by or inability to obtain or keep the necessary authorizations or approvals from any governmental agency or authority, which by exercise of due diligence such Party' could not reasonably have been expected to avoid and which by exercise of due diligence it has been unable to overcome. Nothing contained herein shall be construed as to require a Party to settle any strike or labor dispute in which it may be involved. Either Party rendered unable to fulfill any of its obligations under this Agreement by reason of an uncontrollable force shall give prompt written notice of such fact to the other Party and shall exercise due diligence to remove such inability with all reasonable dispatch. 17. ASSIGNMENTS: 17.1 Any assignment by Edison of its interest in this Agreement which is made without the written consent of IID shall not relieve Edison from its primary liability for any of its duties and obligations hereunder, and in the event of any such assignment Edison shall continue to remain primarily liable for payment of any and all money due IID hereunder and for the performance and observance of all other covenants, duties and obligations to be performed and observed hereunder by it to the same extent as though no assignment has been made. 17.2 Whenever an assignment of Edison's interest in this Agreement is made with the written consent of' IID, Edison's assignee shall expressly assume in writing the duties 20
EX-10.3.3425th Page of 42TOC1stPreviousNextBottomJust 25th
and obligations hereunder of Edison and, within thirty (30) days after any such assignment and assumption of duties and obligations, Edison shall furnish or cause to be furnished to IID a true and correct copy of such assignment and assumption of duties and obligations. 18. GOVERNING LAW: This Agreement shall be interpreted, governed by and construed under the laws of the State of California or the laws of the United States, as applicable. 19. NOTICES: Any notice, demand or request provided for in this Agreement, or served, given or made in connection with it, shall be in writing and shall be deemed properly served, given or made or delivered in person or sent by United States mail, postage prepaid, to the persons specified below unless otherwise provided for in this Agreement: Imperial Irrigation District c/a General Manager P. 0. Box 937 Imperial, California 92551 Southern California Edison Company c/o Secretary P.0. Box 800 Rosemead, California 91770 Either Party may at any time, by notice to the other Party, change the designation or address of the person so specified as the one to receive notices pursuant to this Agreement. 21
EX-10.3.3426th Page of 42TOC1stPreviousNextBottomJust 26th
20. SIGNATURE CLAUSE: The signatories hereto represent that they have been appropriately authorized to enter into this IID-Edison Transmission Service Agreement for Alternative Resources on behalf of the Party for whom they sign. This Agreement is hereby executed as of the 26 day of September, 1985. IMPERIAL IRRIGATION DISTRICT By: /s/ Lloyd W. Allen ----------------------------- Name: Lloyd W. Allen President, Pro Tem Board of Directors SOUTHERN CALIFORNIA EDISON COMPANY By: /s/ Edward A. Myers, Jr. ----------------------------- Name: Edward A. Myers, Jr. Vice President 22
EX-10.3.3427th Page of 42TOC1stPreviousNextBottomJust 27th
EXHIBIT I --------- DEVELOPMENTS AND METHODOLOGIES FOR THE TRANSMISSION AND SUBTRANSMISSION SERVICE CHARGES AND SCHEDULING FEE. ------------------------------------------------------------------------------- EXHIBIT I.A ----------- DEVELOPMENT AND METHODOLOGY FOR THE 92 kV-161 kV-230 kV TRANSMISSION SERVICE CHARGE. EXHIBIT I.B ----------- DEVELOPMENT AND METHODOLOGY FOR THE 34.5 kV SUBTRANSMISSION SERVICE CHARGE. EXHIBIT I.C ----------- METHODOLOGY AND CALCULATION OF SCHEDULING FEE. EI-1
EX-10.3.3428th Page of 42TOC1stPreviousNextBottomJust 28th
EXHIBIT I.A ----------- DEVELOPMENT AND METHODOLOGY FOR THE 92 kV - 161 kV - 230 kV TRANSMISSION SERVICE CHARGE ----------------------------------------------------------- EI.A-1 Development ------------------ Plant Investment ---------------- Transmission @ 12/31/83 OC (2)......................................... $20,700,415 RCN (3)........................................ 88,300,000 Adjusted Investment ------------------- Weighted Plant (4)............................. 40,980,291 Plant Additions in 1984........................ 4,111,000 General Plant (Allocated) (5).................... 120,625 M&S (Allocated) (6).............................. 782,629 ---------- Total Adjusted Investment (TAI).................. $45,994,545 Annual Cost ----------- Fixed Cost @ 13.53% x (TAI) (1).................. $ 6,223,062 Trans. O&M (Allocated) (7)....................... 764,058 A&G (Allocated) (8).............................. 332,847 ----------- Total Annual Cost ............................... $ 7,309,967 Annual Peak Load - (kW) (Includes Wheeling of 63,000 kW) ....................................... 432,000 Cost Per kW Per Year............................... $ 16.92 Cost Per kW Per Month .............................. $ 1.41 ----- ----- EI.A-2 Methodology ------------------ (1) Fixed cost @ 13.53% based upon 10.41% interest rate, 33-year amortization, and 1.25 coverage. This rate is based on the average interest rate for the previous 12 months as obtained from the "Merrill Lynch 500 Municipal Bond Index Electric - Retail". (2) OC = Original Cost; see under Original Cost, "Transmission Plant, Transmission" EI-4 (3) RCN = Reproduction Cost New; see under "Total-RCN"-EI-5 (4) Weighted Plant = 70% OC + 30% RCN EI-2
EX-10.3.3429th Page of 42TOC1stPreviousNextBottomJust 29th
(5) General Plant (Allocated) = General Plant X Trans. O&M (Allocated) ---------------------------------- (Prod. O&M Exc. Fuel) + (Dist. O&M) + (Trans. O&M) + (Dispatching) + (Customer Acctg. and Services) = $1,526,849 X $764,058 ---------------------------------- $3,085,080 + $4,080,868 + $694,545 + $189,540 + $1,621,252 = $1,526,849 X $764,058 = $120,625 ---------- ======== $9,671,285 (6) M&S (Allocated) = M&S X Transmission OC ------------------ Total Elect. Plant = $6,151,304 X $20,700,415 = $782,629 ------------ ======== $162,700,978 (7) Trans. O&M (Allocated) = Trans. O&M X Transmission OC + Dispatching ----------------- Total Trans Plant = $694,545 X $20,700,415 + $189,540 ----------- $25,025,093 = $764,058 ======== (8) A&G (Allocated) = A&G X Trans. O&M (Allocated) -------------------------------------- (Prod. O&M Exc. Fuel) + (Dist. (O&M) +(Trans. O&M) + (Dispatching) + (Customer Acctg. and Services) = $4,086,530 X $764,058 = $322,847 -------------- ======== $9,671,285 EI-3
EX-10.3.3430th Page of 42TOC1stPreviousNextBottomJust 30th
EI-4 IMPERIAL IRRIGATION DISTRICT IID-Edison Transmission ---------------------------- Service Agreement for ELECTRIC PLANT INVESTMENT Alternative Resources ------------------------- 12-31-83 -------- Original Reserved for Depreciated Cost Depreciation Value ---------- ------------ ------------ Production Plant: ---------------- Steam $ 27,669,266 $18,714,813 $ 8,954,453 Hydro 20,837,053 12,515,654 8,321,399 Diesel 2,192,176 1,678,426 513,750 Gas turbines 21,254,581 4,526,058 16,728,523 Heber geothermal 73,884 12,245 61,639 *Other production ------------ ----------- ----------- Total production plant 72,026,960 37,447,196 34,579,764 ------------ ----------- ----------- Transmission Plant: ------------------ Transmission 20,700,415 11,847,260 8,853,155 Subtransmission 4,324,678 1,727,232 2,597,446 ------------ ----------- ----------- Total transmission plant 25,025,093 13,574,492 11,450,601 ------------ ----------- ----------- Distribution Plant: ------------------ Land and land rights 401,433 401,433 Structures and improvements 664,823 328,992 335,831 Station equipment 11,929,448 5,082,909 6,846,539 Poles, towers and fixtures 11,485,005 3,630,291 7,854,714 Overhead conductors and devices 9,389,058 4,708,089 4,680,969 Underground conduit 316,690 78,540 238,150 Underground conductors and devices 4,145,254 703,256 3,441,998 Line transformers 14,523,770 5,878,024 8,645,746 Services 3,386,047 1,825,151 1,560,896 Meters 4,247,559 1,542,261 2,705,298 Street lighting and signal system 2,227,858 963,106 1,264,752 ------------ ----------- ----------- Total distribution plant 62,716,945 24,740,619 37,976,326 ------------ ----------- ----------- General plant 1,526,849 699,191 827,658 Intangible plant 49,379 49,379 Donations in aid of construction - P.W.A. Grant 2,080,920 [ 2,080,920] Contributions in aid of construction 1,590,228 [ 1,590,228] ------------ ----------- ----------- Total electric plant in service 161,345,226 80,132,646 81,212,550 ------------ ----------- ----------- Electric plant acquisition adjustment 719,334 719,334 Electric plant held for future use 636,418 318,712 317,706 ------------ ----------- ----------- Total electric plant $162,700,978 $81,170,692 $81,530,286 ============ =========== =========== Materials and supplies $ 6,151,304 ============ [ ] Deductions * Included in Gas Turbines EI-4
EX-10.3.3431st Page of 42TOC1stPreviousNextBottomJust 31st
REPRODUCTION COST AS OF 12/31.83 EI-5 IID-Edison Transmission (Costs In Millions Of Dollars) Service Agreement for ORIGINAL NET Alternative Resources YEAR COST ADDITIONS HWI TRANSLATOR RCN -------------------- --------------- --------------- ------------- ---------------- ------------- 1938 0.15 0.15 22 11.55 1.73 1939 0.24 0.09 22 11.55 1.04 1940 0.26 0.02 22 11.55 0.23 1941 0.26 0.00 23 11.04 0.00 1942 0.55 0.29 25 10.16 2.95 1943 1.78 1.23 25 10.16 12.50 1944 2.05 0.27 25 10.16 2.74 1945 1.91 -0.14 26 9.77 -1.37 1946 1.85 -0.06 29 8.76 -0.53 1947 2.13 0.28 34 7.47 2.09 1948 2.32 0.19 37 6.86 1.30 1949 3.45 1.13 38 6.68 7.55 1950 4.35 0.90 40 6.35 5.72 1951 4.49 0.14 45 5.64 0.79 1952 6.07 1.58 46 5.52 8.72 1953 6.23 0.16 49 5.18 0.83 1954 6.79 0.56 50 5.08 2.84 1955 7.83 1.04 52 4.88 5.08 1956 8.36 0.53 56 4.54 2.40 1957 9.94 1.58 57 4.46 7.04 1958 10.16 0.22 59 4.31 0.95 1959 10.64 0.48 60 4.23 2.03 1960 10.95 0.31 60 4.23 1.31 1961 11.03 0.08 59 4.31 0.34 1962 11.76 0.73 59 4.31 3.14 1963 11.80 0.04 59 4.31 0.17 1964 12.00 0.20 61 4.16 0.83 1965 12.08 0.08 64 3.97 0.32 1966 12.36 0.28 67 3.79 1.06 1967 12.46 0.10 70 3.63 0.36 1968 13.10 0.64 73 3.48 2.23 1969 13.33 0.23 78 3.26 0.75 1970 14.22 0.89 83 3.06 2.72 1971 14.43 0.21 89 2.85 0.60 1972 14.47 0.04 93 2.73 0.11 1973 14.59 0.12 100 2.54 0.30 1974 15.19 0.60 124 2.05 1.23 1975 15.21 0.02 145 1.75 0.04 1976 15.32 0.11 158 1.61 0.18 1977 15.59 0.27 172 1.48 0.40 1978 15.71 0.12 174 1.46 0.18 1979 15.85 0.14 190 1.34 0.19 1980 16.14 0.29 211 1.20 0.35 1981 18.18 2.04 230 1.10 2.25 1982 20.08 1.90 245 1.04 1.97 1983 20.70 0.62 254 1.00 0.62 --------------- --------------- ------------- ---------------- ------------- TOTAL 20.70 20.70 254 4.27 88.30 (1) Original Cost As Of December 31 Of Each Year Was Obtained From IID Annual Reports And Includes 92 kV And 161 kV Transmission Plant Investment. (2) Handy-Whitman Index For Total Transmission Plant For The Pacific Region Was Utilized To Compute The RCN. (3) RCN - Net Additions * HWI Translator EI-5
EX-10.3.3432nd Page of 42TOC1stPreviousNextBottomJust 32nd
EXHIBIT I.B ----------- DEVELOPMENT AND METHODOLOGY FOR THE 34.5 kV SUBTRANSMISSION SERVICE CHARGE -------------------------------------------- EI.B-1 DEVELOPMENT OF SERVICE CHARGES-BRAWLEY GEOTHERMAL PLANT UNIT NO. 1 -------------------------------------- A. Brawley to Rio Vista -------------------- Miles x OC = 2.8 mi x $7,291/mi = $20,415 AFC = .1353 x $20,415 = $2,762 TL = 21,000 kW O&M = .03 X 20,415 = 612 $/kW-yr = $0.1704 A&G = .01 X 20,415 = 204 $/kW-mo = $0.0142 ------ ======= $/yr. = $3,578 B. Rio Vista to Brawley -------------------- Miles x OC = 1.74 mi x $7,2191/mi = $12,686 AFC = .1353 x $12,686 = $1,716 TL - 31,750 kW O&M = .03 x 12,686 = 381 $/kW-yr = $0.0700 A&G = .01 x 12,686 = 127 $/kW-mo = 0.0058 ------ ======= $/yr. = $2,224 C. Brawley to Rockwood ------------------- Miles x OC = 0.96 mi x $7,291/mi = $6,999 AFC = .1353 x $6,999 = $ 947 TL = 53,000 kW O&M = .03 x 6,999 = 210 $/kW-yr = $0.0232 A&G - .01 x 6,999 = 70 $/kW-mo = $0.0019 ------ ======= $/yr. = $1,227 SUMMARY OF CHARGES ------------------ A + B + C = $ (0.0142 + 0.0058 + 0.0019) /kW-mo. = $0.0219/kW mo. Rounded to: $0.022/kW-mo. ============= EI-6
EX-10.3.3433rd Page of 42TOC1stPreviousNextBottomJust 33rd
EI.B-2 DEVELOPMENT OF SERVICE CHARGES - SALTON SEA GEOTHERMAL PLANT UNIT NO. 1 ------------------------------------------- A. SALTON SEA TO CALIPATRIA ------------------------ Miles x OC = 10.8 mi x $7,291/mi = $78,743 AFC = .1353 x $78,743 = $10,654 TL = 9,000 kW O&M = .03 X $78,743 = 2,362 $kW-yr = $1.5337 A&G = .01 X $78,743 = 787 $kW-mo = $0.1278 ------- ======= $/yr. = $13,803 B. Calipatria to Brawley --------------------- Miles x OC = 9.9 mi x $7,291/mi = $72,181 AFC = .1353 x $72,181 = $ 9,766 TL = 15,000 kW O&M = .03 x 72,181 = 2,165 $/kW-yr = $0.8435 A&G = .01 x 72,181 = 722 $/kW-mo = $0.0703 ------- ======= $/yr. = $12,653 C. Brawley to Rio Vista -------------------- Miles x OC = 2.8 mi x $7,291/mi = $20,415 AFC = .1353 x $20,415 = $ 2,762 TL = 21,000 kW O&M = .03 x 20,415 = 612 $/kW-yr = $0.1704 A&G = .01 x 20,415 = 204 $/kW-mo = $0.0142 -------- ======= $/yr. = $3,578 D. Rio Vista to Brawley -------------------- Miles x OC = 1.74 mi x $7,291/mi = $12,686 AFC = .1353 x $12,686 = $1,716 TL = 31,750 kW O&M = .03 x 12,686 = 381 $/kW-yr = $0.0700 A&G = .01 x 12,686 = 127 $/kW-mo = 0.0058 ------- ======= $/yr. = $2,224 E. Brawley to Rockwood ------------------- Miles x OC = 0.96 mi x $7,291/mi = $6,999 AFC = .1353 x $6,999 = $ 947 TL = 53,000 kW O&M = .03 x 6,999 = 210 $/kW-yr = $0.0232 A&G = .01 x 6,999 = 70 $/kW-mo = $0.0019 ------- ======= $/yr. = $1,227 SUMMARY OF CHARGES ------------------ A + B + C + D + E = $ (0.1278 + 0.0703 + 0.0142 + 0.0058 + 0.0019)/kW mo. = $0.2200/kW-mo. Rounded to: $0.22/kW-mo. =========== EI-7
EX-10.3.3434th Page of 42TOC1stPreviousNextBottomJust 34th
EI.B-3 DEVELOPMENT OF SERVICE CHARGES FOR MAGMA EAST MESA GEOTHERMAL PLANT UNIT NO. 1 ---------------------------------------- A. East Mesa to Magma (TAP) ------------------------ Miles x OC = 6.37 mi x $7,291/mi = $46,444 AFC = .1353 x $46,444 = $6,284 TL = 5,000 kW O&M = .03 x 46,444 = 1,393 $/kW-yr = $1.6282 A&G = .01 x 46,444 = 464 $/kW-mo = $0.1357 ------ ======= $/yr. = $8,141 B. Magma (Tap) to Holtville ------------------------ Miles x OC = 4.33 mi x $7,291/mi = $31,570 AFC = .1353 x $31,570 = $4,271 TL = 5,700 kW O&M = .03 x 31,570 = 947 $/kW-yr = $0.9709 A&G - .01 x 31,570 = 316 $/kW-mo = $0.0809 ------ ======= $/yr. = $5,534 SUMMARY OF CHARGES ------------------ A + B = $(0.1357 + 0.0809) /kW mo. = $0.2166/kW-mo. Rounded to: $0.22/kW-mo. =========== EI-8
EX-10.3.3435th Page of 42TOC1stPreviousNextBottomJust 35th
EI.B.A METHODOLOGY FOR 34.5 kV SUBTRANSMISSION SERVICE CHARGE ------------------------------------------------------ (1) Original Cost (OC): OC = Curr. $/mi x 1964 HW ------- 1984 HW HW=Handy-Whitman Index for Total Transmission Plant For The Pacific Region Curr. $/mi - $30,000/mi 1964 HW = 61 1984 HW 251 OC = $30,000/mi x 61 = $30,000/mi x 0.2430 ----- 251 = $7291/mi (2) O&M = 3% of OC (3) A&G = 1% of OC (4) Annual Fixed Cost (AFC) = 13.53% of OC; 13.53% is as defined in EI.A-2(1) (5) Transmission Loading (TL) = absolute value of line loadings. (6) $/kW-yr = $/yr divided by TL (7) For mileages see EI-10 EI-9
EX-10.3.3436th Page of 42TOC1stPreviousNextBottomJust 36th
EI-10 ONE LINE DIAGRAM OF SUBTRANSMISSION PATH FOR EXISTING GEOTHERMAL UNITS [Graphic: Simplified IID Transmission Diagram] NOTE: DIAGRAM DEPICTS SHORTEST 34.5 KV PATH TO 92 KV TRANSMISSION-NETWORK LOADS REPRESENT 1984 ESTIMATED SUMMER PEAK LOADS EI-10
EX-10.3.3437th Page of 42TOC1stPreviousNextBottomJust 37th
EXHIBIT I.C METHODOLOGY AND CALCULATION OF SCHEDULING FEE ---------------------------------------------------- ANNUAL DETERMINATION OF IID SCHEDULING FEES --------------------- IID, prior to January 1 of each year, will calculate monthly fees for scheduling services related to Alternative Energy Resources and transactions with other utilities as follows: A. An appropriate number of scheduling units will be assigned to every IID resource, Alternative Energy Resource, and transaction with other utilities. The number of scheduling units assigned to each resource and/or transaction will depend upon the total daily number of functions and therefore, estimated time required to schedule the resource and/or transaction. This estimate will be directly related to the complexity of the scheduling service being provided. Table 1 provides an example of how the total scheduling units will be determined for the 1985 IID system. B. The expenses related to dispatching and scheduling services will be equal to the sum of the following: 1. FPC Account 556, as provided by the IID budget for the appropriate year, and 2. A portion of the annual expenses related to the SCADA and AGC systems. The portion of the annual expenses related to the SCADA and AGC systems will be determined by multiplying the levelized debt service payments for the systems by the percentage that FPC Account 556 is of the total of FPC Accounts 556, 561 and 581. Table 2 provides an example of the calculations involved with this step. C. The annual scheduling fee per scheduling unit will be determined by dividing the expenses related to scheduling found in Step 8 by the total scheduling units from Step A. The per unit fee will then be multiplied by the number of scheduling units assigned to each resource and/or transaction to develop an appropriate annual scheduling fee for that resource and/or transaction. The monthly scheduling fee will then be calculated by dividing the annual fee by 12. Table 3 provides an example of this step for 1985. 7-26-85 EI-11
EX-10.3.3438th Page of 42TOC1stPreviousNextBottomJust 38th
Table 1 Imperial Irrigation District SCHEDULING FEE METHODOLOGY DETERMINATION OF TOTAL SCHEDULING UNITS --------------------------------------- Hours Payback/ On AGC OFF Energy Capacity Variable Banking Prescheduling System System (X=2) (X=2) (X=1) (X=2) (X=1) (X=1) (X=1) ------ -------- -------- -------- ------------- -------- -------- IID's Generating Units: Pilot Knob........................ x x x x Drop #1 .......................... x x x x Drop #2 .......................... x x x x Drop #3 .......................... x x x x Drop #4 .......................... x x x x Drop #5 .......................... x x x x East Highline .................... x x x x Turnip & Double Weir ............. x x x x E1 Centro Unit #3 ................ x x x x E1 Centro Unit $4 ................ x x x x Coachella Units #1 & #2........... x x x x Coachella Units #3 & #4........... x x x x Rockwood ......................... x x x x Brawley .......................... x x x x Brawley Diesels .................. x x x x Alternative Energy Resources: Salton Sea ....................... x x x x x x Magma (East Mesa) ................ x x x x x x Brawley .......................... x x x x x x Dravo ............................ x x x x x x Heber Binary ..................... x x x x x x Transactions with Other Utilities: DOE .............................. x x x x x EPE .............................. x x x x x SCE .............................. x x x x x x SUGAE ............................ x x x x x APS (Yucca) ...................... x x x x x SCE GIs (Axis) ................... x x x x x x APS (Axis) ....................... x x x x x YCMUA ............................ x x x x x x Loss Accounting (X=1) Total ---------------- ----- IID's Generating Units: Pilot Knob........................ 6 Drop #1 .......................... 6 Drop #2 .......................... 6 Drop #3 .......................... 6 Drop #4 .......................... 6 Drop #5 .......................... 6 East Highline .................... 6 Turnip & Double Weir ............. 6 E1 Centro Unit #3 ................ 6 E1 Centro Unit $4 ................ 6 Coachella Units #1 & #2........... 6 Coachelle Units #3 & #4........... 6 Rockwood ......................... 6 Brawley .......................... 6 Brawley Diesels .................. 6 ----- Subtotal ................. 90 Alternative Energy Resources: Salton Sea ....................... 9 Magma (East Mesa) ................ 9 Brawley .......................... 9 Dravo ............................ x 10 Heber Binary ..................... x 10 ----- Subtotal ................ 47 Transactions with Other Utilities: DOE .............................. 7 EPE .............................. 7 SCE .............................. 9 SUGAE ............................ x 8 APS (Yucca) ...................... 7 SCE GIs (Axis) ................... 9 APS (Axis) ....................... 7 YCMUA ............................ 7 ----- Subtotal ................ 61 Total Scheduling Units 198 ----- 7-24-85 EI-12
EX-10.3.3439th Page of 42TOC1stPreviousNextBottomJust 39th
Table 2 Imperial Irrigation District SCHEDULING FEE METHODOLOGY EXPENSES RELATED TO SCHEDULING ------------------------------ IID 1985 Budget --------------- FPC Account 556 $158,600 (29.1%) FPC Account 561 237,500 (43.5%) FPC Account 581 149,300 (27.4%) -------- Total $545,400 (100.0%) SCADA and AGC Systems --------------------- Total Investment $6,200,000 Annual Expense 6,200,000 x .1170923(1) = $ 725,972 Expenses Related to Scheduling ------------------------------ FPC Account 556 $158,600 29.1% of SCADA and AGC Systems Annualized Expense (725,972 x .291) 211,258 -------- Total Expenses Related to Scheduling $369,858 (1) Capital Recovery Factor determined from levelized debt service payments of $7,611,000 for $65,000,000 May, 1983 Bond Issue. 7-25-85 EI-13
EX-10.3.3440th Page of 42TOC1stPreviousNextBottomJust 40th
Table 3 Imperial Irrigation District SCHEDULING FEE METHODOLOGY CALCULATION OF SCHEDULING FEE ----------------------------- Annual Charge Per Scheduling Unit --------------------------------- Total Expenses Related to Scheduling (From Table 2) $369,858 Total Scheduling Units (From Table 1) 198 -------- Annual Charge per Scheduling Unit (369,858/198) $ 1,868/year Alternative Energy Resource Scheduling Fee ------------------------------------------ Salton Sea, Magma (East Mesa), Brawley: Annual Charge (9 Scheduling Units x $1,868) $ 16,812/year Monthly Charge ($16,812 divided by 12) $ 1,401/month (1) Bravo and (2) Heber Binary: Annual Charge (10 Scheduling Units x $1,868) $18,680/year (3) Monthly Charge ($18,680 divided by 12) $ 1,557/month NOTES: ----- (1) Bravo = Heber Geothermal Company Exhibit V. (2) Heber Binary - SDG&E Binary Geothermal Unit not included in this IID-Edison Transmission Service Agreement for Alternative Resources. (3) Also applies as initial Monthly Fee for Plants in Exhibits VI, VII and VIII. 7-26-85 EI-14
EX-10.3.3441st Page of 42TOC1stPreviousNextBottomJust 41st
EXHIBIT V --------- TRANSMISSION SERVICE FOR THE HEBER GEOTHERMAL POWER PLAN UNIT NO. 1 ---------------------------------------------- EV-1. DESCRIPTION: The Heber Geothermal Power Plant Unit No. 1 at 52 MW (gross) located in the Heber Known Geothermal Resource Area of the Imperial Valley. EV-2. APPLICABILITY: Applicable to the transmission service to be provided by IID to Edison for transmitting the electrical output from the Heber Geothermal Plant Unit No. 1 Point of Receipt to the Point(s) of Delivery. EV-3. PLANT CONNECTION AGREEMENT: The Heber Geothermal Plant Connection Agreement to be executed between IID and Heber Geothermal Company. EV-4. TRANSMISSION SERVICE ENTITLEMENT: 47 MW or the amount provided in accordance with Section 6.2. EV-5. POINT OF RECEIPT: Heber Geothermal Power Plant Unit No. 1 Switchyard, 92 kV Bus. EV-6. POINT(S) OF DELIVERY: Points of Interconnection or Blythe Substation. EV-7. TERM: The term of the Transmission Service Entitlement for the Heber Geothermal Power Plant Unit No. 1 shall be effective from the Date of Initial Service and shall be effective from the Date of Initial Service and shall terminate on the earliest of: (i) December 31, 2015, or (ii) twenty-four (24) months from the date Unit No. 1 has ceased to operate as determined by IID, or (iii) the termination date of the Plant Connection Agreement, or (iv) the date agreed to by the Authorized Representative. EV-8. TRANSMISSION SERVICE CHARGE: $1.41 per kilowatt-month, or as revised in accordance with Section 8.2, times Transmission Service Entitlement. EV-9. SCHEDULING FEE: $1557 per month or as revised in accordance with Section 8.3. EV-10. TRANSMISSION LOSSES: 4.1% or as revised in accordance with Section 7. EI-18
EX-10.3.34Last Page of 42TOC1stPreviousNextBottomJust 42nd
EXHIBIT VIII ------------ TRANSMISSION SERVICE FOR THE ORMESA GEOTHERMAL POWER PLANT UNIT NO. 1 ------------------------------------------------ EVIII-1. DESCRIPTION: The Ormesa Geothermal Power Plant Unit No. 1 at 30 MW (gross) located in the East Mesa Known Geothermal Resource Area of the Imperial Valley. EVIII-2. APPLICABILITY: Applicable to the transmission service to be provided by IID to Edison for transmitting the electrical output from the Ormesa Geothermal Power Plant Unit No. 1 from the Point of Receipt to the Point(s) of Delivery. EVIII-3. PLANT CONNECTION AGREEMENT: The Ormesa Geothermal Plant Connection Agreement to be executed between IID and Ormesa Geothermal. EVIII-4. TRANSMISSION SERVICE ENTITLEMENT: 24 MW or the amount provided in accordance with Section 6.2. EVIII-5. POINT OF RECEIPT: Ormesa Geothermal Power Plant Unit No. 1 Switchyard, 92 kV Bus. EVIII-6. POINT(S) OF DELIVERY: Points of Interconnection or Blythe Substation. EVIII-7. TERM: The term of the Transmission Service Entitlement for the Ormesa Geothermal Power Plan Unit No. 1 shall be effective from the Date of Initial Service and shall terminate on the earliest of: (i) December 31, 2015, or (ii) twenty-four (24) months from the date Unit No. 1 has ceased to operate as determined by IID, or (iii) the termination date of the Plant Connection Agreement, or (iv) the date agreed to by the Authorized Representatives. EVIII-8. TRANSMISSION SERVICE CHARGE: $1.41 per kilowatt-month, or as revised in accordance with Section 8.2, times Transmission Service Entitlement. EVIII-9. SCHEDULING FEE: $1557 per month or as revised in accordance with Section 8.3. EVIII-10. TRANSMISSION LOSSES: 5.4% or as revised in accordance with Section 7. EI-21

Dates Referenced Herein

Referenced-On Page
This ‘S-1/A’ Filing    Date First  Last      Other Filings
12/31/151042None on these Dates
Filed on:9/28/04
 List all Filings 


2 Subsequent Filings that Reference this Filing

  As Of               Filer                 Filing    For·On·As Docs:Size             Issuer                      Filing Agent

 2/25/22  Ormat Technologies, Inc.          10-K       12/31/21  143:66M                                    RDG Filings/FA
 2/26/21  Ormat Technologies, Inc.          10-K       12/31/20  144:33M                                    RDG Filings/FA
Top
Filing Submission 0000950136-04-003123   –   Alternative Formats (Word / Rich Text, HTML, Plain Text, et al.)

Copyright © 2024 Fran Finnegan & Company LLC – All Rights Reserved.
AboutPrivacyRedactionsHelp — Fri., Apr. 26, 7:55:55.1am ET